14.2.1.58 Binary output: MODES: Man mode
The output is closed while the controller is currently in MAN mode (either
switched by the mode selector on the front panel or by the input Remote
MAN).
14.2.1.59 Binary output: MODES: Aut mode
The output is closed while the controller is currently in AUT mode (either
switched by the mode selector on the front panel or by the input Remote
AUT).
14.2.1.60 Binary output: MODES: Test mode
The output is closed while the controller is currently in TEST mode (either
switched by the mode selector on the front panel or by the input Remote
TEST).
14.2.1.61 Binary output: MainsParams OK
This output indicates that the mains is healthy. The output is closed while all
mains electrical parameters are in limits. If MCB is closed, the output
deactivates after the the delay for fixed voltage or frequency protections
elapses. If MCB is opened, the output deactivates immediately after electrical
parameters get out of limit (e.g. frequency, voltage, voltage unbalance etc.).
14.2.1.62 Binary output: Bus Params OK
This output indicates that the bus is healthy. The output is closed while all
bus electrical parameters are in limits.
14.2.1.63 Binary output: TimerAct 1-4
This is combined output from timer channels 1-4. The output is closed if at