InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
This setpoint adjusts the relative integration factor (I-factor) of the voltage
control PI loop. The gain factor (P-factor) for the voltage control loop is
adjusted by the setpoint Voltage gain.
VOLTAGE GAIN AND VOLTAGE INT SETPOINTS ARE ACTIVE DURING:
reverse synchronization of the gen-set group back to the
mains
forward or reverse synchronization of the gen-set group to the
mains
synchronization between “left” and “right” buses
NOTE:
See the chapter Regulation loops overview for general information about
regulation loops and their adjustment.
11.2.11.3 Setpoint: PF gain
This setpoint adjusts the gain factor (P-factor) of the cos-phi control PI loop.
The integration factor (I-factor) for the cos-phi control loop is adjusted by the
setpoint PF int.
NOTE:
If this setpoint is set to 0 the regulation loop is disabled.
PF gain and PF int setpoints are active only when gen-sets run in parallel to
mains.
NOTE:
See the chapter Regulation loops overview for general information about
regulation loops and their adjustment.
11.2.11.4 Setpoint: PF int