InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
156
11.2.1.5 Setpoint: Import load
Group
Process Control
Range [units]
-32000 .. 32000 [kW]
Related FW
standard v3.1.0
Description
This setpoint is used for adjusting of the requested mains import if the load
control mode is set to IMP/EXP (#SysLdCtrl PtM = LDSHARING and MLoad
ctrl PtM = IMP/EXP)
This setpoint is also used for adjusting of the maximum allowed export if
export limit function is active (Export limit = ENABLED).
NOTE:
Negative value of import is export, i.e. the power flows into the mains.
NOTE:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
11.2.1.6 Setpoint: Import PF
Group
Process Control
Range [units]
0.60 .. 1.20 [-]
Related FW
standard v3.1.0
Description
The setpoint is used to adjust the requested power factor at the mains in
import/export mode (i.e. #SysPFCtrl PtM = VSHARING and PF ctrl PtM =
IMP/EXP).
Values over 1.00 mean capacitive load character, i.e. setting 0.95 means
0.95L and setting 1.05 means 0.95C.
11.2.1.7 Setpoint: MLoad ctrl PtM
Group
Process Control
Range [units]
SYSBLD->LS, ANEXSYSBLD->LS, IMP/EXP, ANEXT IMP/EXP, T BY PWR
[-]
Related FW
standard v3.1.0
Force value
possible
YES