InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
152
LOADSHARING MODE
#SysLdCtrl PtM = LDSHARING,
Load ctrl PtM = SYSBLD->LS
The system
baseload is
maintained by
the IM-NT over
the load
sharing.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.1.2 Setpoint: #SysPwrFactor
Group
Process Control
Range [units]
0.60 .. 1.20 [-]
Related FW
standard v3.1.0
Description
The setpoint is used for adjusting the requested base power factor of the
gen-sets in the parallel-to-mains operation. The setpoint #SysPFCtrl PtM
must be set to BASEPF for constant power factor control. The power factor of
each gen-set is controlled by it's own PF control loop and InteliMains does
not play active role in this type of control.
Settings 0.60 0.99 correspond to inductive PF (0.60L - 0.99L), 1.01 1.20
correspond to capacitive PF (0.99C - 0.80C).
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.1.3 Setpoint: #SysLdCtrl PtM
Group
Process Control
Range
[units]
BASELOAD, LDSHARING [-]
Related
FW
standard v3.1.0
Descriptio
n
This setpoint is used to adjust the load control type in parallel-to-mains operation.