InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
157
Description
The setpoint is used for selection of the load control mode in parallel to mains
operation if the load is controlled by the InteliMains (i.e. #SysLdCtrl PtM =
LDSHARING).
SYSBLD->LS
The load of the gen-set group is maintained at
constant level adjusted by the setpoint
#SysBaseLoad.
ANEXSYSBLD->LS
The load of the gen-set group is maintained at
constant level given by the analog input
MLC:AnExSysBld.
IMP/EXP
The load of the gen-set group is controlled so,
that the mains import is maintained constant at
the level adjusted by setpoint Import load.
ANEXT IMP/EXP
The load of the gen-set group is controlled so,
that the mains import is maintained constant at
the level given by the analog input MLC:AnExI/E.
T BY PWR
The load of the gen-set group is controlled so,
that the analog input MLC:TByPwr is maintained
at constant level given by setpoint TempByPwr
Treq. The regulation loop is adjusted by setpoints
TempByPwr gain and TempByPwr int.
NOTE:
If the system baseload value needs to be changed remotely via a
communication interface select the ANEXSYSBLD->LS mode and then
configure one of the objects ExtValue1 .. ExtValue4 as the source for the
analog input MLC:AnExSysBld. These objects can be written remotely via
communication (e.g. via MODBUS).
CAUTION!
Do not use cyclic write of the baseload setpoint for remote load control. It
may cause the internal EEPROM memory damage.
11.2.1.8 Setpoint: Soft Unload
Group
Process Control
Range [units]
STANDARD, AuxCTGen, AuxCTLoad [-]
Related FW
standard v3.1.0
Description
This setpoint adjusts the way MGCB opening is evaluated in case of unloaded