InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
>LS, ANEXSYSBLD->LS or T BY PWR.
NOTE:
If the import value/setpoint is negative, it actually means export. This function
can be used to protect the system from unwanted export. You may set
maximum export value or you can set it possitive to keep some import even
in cases that there are abrupt load changes.
NOTE:
See the setpoint I/E-Pm meas for details about mains import measurement
methods.
11.2.1.19 Setpoint: TempByPwr Treq
The setpoint is used for adjusting the requested temperature for the
Temperature-By-Power control loop.
The Temperature-By-Power is active if the setpoint Load ctrl PtM is set to T
BY PWR position and the logical analog input MLC:TByPwr is attached to the
physical analog input where the temperature is measured.
See also the setpoints TempByPwr int and TempByPwr gain.
NOTE:
As the "regulating action" of the Temperature-By-Power control loop is
changing of the group power the regulated value (i.e. some temperature)
must depend on the group power. Typical usage of this function is regulation
of the output temperature of the heating water in a group of CHP units.
11.2.1.20 Setpoint: TempByPwr gain
This setpoint is used to adjust the gain factor for the Temperature-By-Power
control loop. See also the setpoints TempByPwr Treq and TempByPwr int.