11.2.1.21 Setpoint: TempByPwr int
Group
Process control
Range [units]
0.00 .. 100.00 [%]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust the integration factor for the Temperature-By-
Power control loop. See also the setpoints TempByPwr Treq and
TempByPwr gain.
11.2.1.22 Setpoint: Overheat prot
Group
Process control
Range [units]
DISABLED, ENABLED
Related FW
standard v3.1.0
Force value
possible
YES
Description
The setpoint is used to enable/disable the Overheat protection, which is used
for limitation of the group power when there is not enough heat outlet from
the gen-set group to avoid shutdown due to oveheating.
If the Overheat protection is enabled and the temperature at the logical
analog input MLC:TByPwr:
increases over the setpoint TempByPwr Treq, the Temperature-By-
Power load control loop is temporarily activated to reduce the power
and consequently the temperature.
returns back under the setpoint TempByPwr Treq, the Temperature-
By-Power regulation loop is deactivated and previous load control
mode (e.g. Baseload) takes place.
NOTE:
See more information about the Temperature-By-Power load control mode in
the description of the setpoint TempByPwr Treq.
11.2.1.23 Setpoint: Island enable
Group
Process Control
Range [units]
NO, YES [-]