The setpoints adjusts the delay for automatic Peak kVA start/stop function.
Set 0 (OFF) to disable Peak kVA automatic start function. See also the
setpoints Peak kVA Start and Peak kVA Stop.
NOTE:
The delay for this function is counted down in any mode if the conditions are
fulfilled (i.e. in OFF when the Mains Import in kVA is higher than Peak kVA
Start).
11.2.1.18 Setpoint: Export limit
The setpoint is used to enable and disable the Export limit function. If the
function is enabled, the group power is limited so that mains import is always
higher or equal to the setpoint Import Load.
PRINCIPLE OF THE EXPORT LIMIT FUNCTION
This function can be used if the setpoint Load Ctrl PtM is set to SYSBLD-