InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
163
NOTE:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
11.2.1.16 Setpoint: Peak kVA Stop
Group
Process control
Range [units]
0 .. Peak kVA Start [kW]
Related FW
standard v3.1.0
Force value
possible
YES
Description
If the object apparent consumption (Object P to the power of 2 + Object Q to
the power of 2) drops below this setpoint for time longer than PeakKVAS/S
del, the gen-set stops automatically (in SPtM application) or gen-set group is
stopped by InteliMains. See also the setpoint Peak kVA Start.
NOTE:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
11.2.1.17 Setpoint: PeakKVAS/S del
Group
Process control
Range [units]
OFF, 1 .. 3200 [s]