InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
11.2.1.14 Setpoint: PeakAutS/S del
The setpoints adjusts the delay for automatic Peak start/stop function. Set 0
(OFF) to disable Peak automatic start function. See also the setpoints
PeakLevelStart and PeakLevelStop.
NOTE:
The delay for this function is counted down in any mode if the conditions are
fulfilled (i.e. in OFF when the Mains Import in kW is higher than
PeakLevelStart).
11.2.1.15 Setpoint: Peak kVA Start
Peak kVA Stop .. 32000 [kVA]
If the object apparent consumption (Object P to the power of 2 + Object Q to
the power of 2) exceeds this setpoint for time longer than PeakKVAS/S del,
the gen-set starts automatically (in SPtM application) or group of gen-sets is
started by InteliMains. Adjusting the PeakKVAS/S del to 0 (OFF) disables the
autostart. See also the setpoint Peak kVA Stop.