InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
162
11.2.1.14 Setpoint: PeakAutS/S del
Group
Process control
Range [units]
OFF, 1 .. 3200 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
The setpoints adjusts the delay for automatic Peak start/stop function. Set 0
(OFF) to disable Peak automatic start function. See also the setpoints
PeakLevelStart and PeakLevelStop.
NOTE:
The delay for this function is counted down in any mode if the conditions are
fulfilled (i.e. in OFF when the Mains Import in kW is higher than
PeakLevelStart).
11.2.1.15 Setpoint: Peak kVA Start
Group
Process control
Range [units]
Peak kVA Stop .. 32000 [kVA]
Related FW
standard v3.1.0
Force value
possible
YES
Description
If the object apparent consumption (Object P to the power of 2 + Object Q to
the power of 2) exceeds this setpoint for time longer than PeakKVAS/S del,
the gen-set starts automatically (in SPtM application) or group of gen-sets is
started by InteliMains. Adjusting the PeakKVAS/S del to 0 (OFF) disables the
autostart. See also the setpoint Peak kVA Stop.