InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
432
ANALOG VALUE
COS PHI FACTOR
<60
0.6L
60 .. 100
0.6L .. 1.00
101 .. 120
0.99C .. 0.80C
15.2.1.5 Analog input: MLC:I/E-Pm
Related FW
standard v3.1.0
Description
This functional input is used for connecting of an external device, which
measures the active power imported from the mains. The device is
connected to the controller via an analog input (e.g. -20 .. 20mA). The
setpoint I/E-Pm meas must be set to the ANALOG INPUT position for this
case.
15.2.1.6 Analog input: MPF:I/E-Qm
Related FW
standard v3.1.0
Description
This functional input is used for connecting of an external device, which
measures the reactive power imported from the mains. The device is
connected to the controller via an analog input (e.g. -20 .. 20mA). The
setpoint I/E-Qm meas must be set to the ANALOG INPUT position for this
case.
15.2.1.7 Analog input: LCD brightness
Related FW
standard v3.1.0
Description
This functional input is used to adjust the backlight intensity of the IG-NT
built-in terminal (display) by an analog input (e.g. a potentiometer). If this
input is configured to a physical analog input or other value, the brightness
adjusted by buttons at the terminal is overriden by this analog input.
15.2.1.8 Analog input: Cold temp 1
Related FW
standard v3.1.0
Description
If there is an additional terminal board between a thermocouple and the IS-
AIN8 module and there is a significant temperature difference between this
terminal board and the module, it is necessary to measure the temperature at