InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
Figure: Adding of various modules
SHBOUT (1) SHBIN (1)
SHBOUT (2)
Not Received
Module SHBIN (2) is not
inserted
SHBOUT (3)SHBIN (3)
SHBIN (2)
Not Received
Module SHBIN (3) is not
inserted
Not Received
Module SHBIN (1) is not
inserted
CAN
CAN
Controller 1 Controller 2
Controller 3
Figure: Principal Scheme (same for shared Binary I/O and shared Analogue I/O
Shared Binary Inputs and Outputs may be used exactly in the same way as standard physical Inputs
and Outputs. If SHBIN or SHAIN modules are configured, at least one corresponding module of
SHBOUT or SHAOUT (respectively) is needed. If it is not configured, corresponding protection
appears because SHBIN or SHAIN will be missing. See the figure below for more information.
NOTE:
If SHUTDOWN (RED) protection is chosen, it is interpreted in InteliMains as Mains Protect with Reset
type protection. For more information on Protection types and alarms please refet to the chapter
Protection and Alarms management.
CAUTION!
For proper function of Shared Binary and Analog Inputs and Outputs, only one source of Shared
Binary or Analog Outputs must be configured (i.e. it is not possible to configure in one controller
SHBOUT1 and to another one as well SHBOUT1).
HINT
Controller sends Shared Binary Outputs each 100ms if there are any changes in any bit position. If
there are no changes, controller sends the information with period 1s.