InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
173
11.2.1.29 Setpoint: Mains coupling
Group
Process Control
Range [units]
ENABLED, DISABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint selects how the IM-NT cooperates with other IM-NT in systems
where one common busbar is supplied from many mains incomers, which are
controlled by many IM-NT controllers.
ENABLED
If there is voltage on Bus, however it is supplied from
other mains incomer controlled by other IM-NT, the
respective IM-NT may also close its MCB and MGCB and
it will couple the two mains incomers together.
DISABLED
The IM-NT will not close it's MCB and MGCB if there is
other IM-NT with closed MCB and MGCB detected on the
CAN2 bus (in the same control group - control groups may
be connected together via Group Link).
NOTE:
Passive phase/voltage check is performed before mains coupling.
11.2.1.30 Setpoint: AUT ctrl mode
Group
Process Control
Range [units]
NORMAL, COX(FOLLOW) [-]
Related FW
standard v3.1.0
Description
This setpoint selects how the MCB is handled in AUT mode.
NORMAL
The MCB is controlled by IM-NT and it's internal
sequences and adjusted timers.
COX(FOLLOW)
The MCB is expected to be controlled by an external
device (e.g. a PLC) and the IM-NT only follows it's
position. Synchronizing can be activated by the input