InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
transferred to gen-sets. After pressing MCB button
MCB is opened and MGCB stays closed, gen-sets are
running in Island operation.
Test on load - MGCB is closed, gen-sets synchronized
to the bus, load transferred to gen-sets and MCB
opened. Return of the load to the Mains is adjusted via
setpoint ReturnTo mains.
11.2.2.18 Setpoint: ContrInitMode
PREVIOUS, OFF, MAN, AUT, [-]
This setpoint adjusts which mode will be activated when the controllers is
powered on.
11.2.2.19 Setpoint: Local buttons
PANEL, EXTBUTTONS, BOTH [-]
The setpoint selects which set of control buttons is currently active. Its function
depends on which type of controller is used. Please refer to the section which
suits your controller/display version.
First section deals with the case of IGS-NT with built-in monochrome
display.
Second section deals with the case of IGS-NT-BB with IV5 display.
Third section deals with the case of IGS-NT-BB with IV8.
NOTE:
If you have IGS-NT (built-in display) and you use additional IV display all the
sections may be relevant (depending on the type of additional displays).
IGS-NT (built-in monochrome display)
The built-in buttons on the controller front panel (IG-NT) or
terminal #1 (IS-NT) are enabled, the binary inputs for
external buttons are disabled.
The built-in buttons are disabled and the binary inputs for