InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp – April 2015
11.2.9.29 Setpoint: #RunHrsMaxDiff
This setpoint adjusts the "deadband" for the running hours equalization
function. The priorities are swapped not until the relative engine hours (RHE)
difference is higher than this deadband.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.30 Setpoint: #PwrBandContr 1
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
This setpoint is used to select the gen-sets which will run within the power
band #1 if the optimalization according to gen-set size is active. Learn more
about this topis in the chapter Gen-set size optimalization.
NOTE:
The combinations of gensets must be created so, that the total nominal
power of the Power band #1 < #2 < #3 < #4.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.31 Setpoint: #PwrBandContr 2
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
This setpoint is used to select the gen-sets which will run within the power
band #2 if the optimalization according to gen-set size is active. Learn more