InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
354
display connected via CAN2 or a PLC connected to the RS485 and
communicating via MODBUS.
13.2.1.27 Binary input: Load res 2
Related FW
standard v3.1.0
Description
This input is used to activate the load reserve set #2 instead of the set #1,
which is active by default. The set #2 is adjusted by setpoints:
#LoadResStrt 2 and #LoadResStop 2 if the power management is
switched to absolute mode
#%LdResStrt 2 and #%LdResStop 2 if the power management is
switched to relative mode.
CAUTION!
All controllers cooperating together in Power management must have the
same load reserve set selected.
NOTE:
It is possible to use virtual peripheries for distribution of the binary signal from
one physical switch connected to one controller to all other controllers over
the CAN bus.