This output is intended for control of the MCB if a contactor is used as MCB. The
output provides continuous signal while the MCB has to be closed. See timing
diagram of all available breaker control outputs at the bottom of this description.
NOTE:
Use invert function when configuring the output in GenConfig to obtain inverted
function of the output, i.e. output is closed while the MCB has to be open.
There are also other outputs availabe for MCB control:
MCB ON coil
MCB OFF coil
MCB UV coil
TIMING OF BREAKER CONTROL OUTPUTS