how to control the output from InteliMonitor and the Modbus chapter in the
latest communication guide for information about control the output using
Modbus.
14.2.1.111 Binary output: RemoteControl8
Related FW
standard v3.1.0
Description
This is a general purpose output, which can be closed and opened remotely,
e.g. from InteliMonitor using the "Remote switches" tool or via MODBUS
using the register #46361 and command #26.
NOTE:
See the Remote switches chapter in the InteliMonitor help for details about
how to control the output from InteliMonitor and the Modbus chapter in the
latest communication guide for information about control the output using
Modbus.
14.2.1.112 Binary output: ModbusSw 1
Related FW
standard v3.1.0
Description
This logical binary output gets activated when the corresponding bit is written
to the Modbus register number 46337. The mirror of the written value can be
also seen in the value ModbusSw1.
EXAMPLE:
If value 255 is written in the Modbus register number 46337, first eight
ModbusSw logical binary outputs get activated.
14.2.1.113 Binary output: ModbusSw 17
Related FW
standard v3.1.0
Description
This logical binary output gets activated when the corresponding bit is written
to the Modbus register number 46338. The mirror of the written value can be
also seen in the value ModbusSw2.
EXAMPLE:
If value 255 is written in the Modbus register number 46338, first eight
ModbusSw logical binary outputs get activated.