EasyManua.ls Logo

ComAp InteliMains NT IM-NT-BB - Page 79

ComAp InteliMains NT IM-NT-BB
437 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
79
7.6.2.3 Priorities
The priority of the gen-set within the group is given by the setpoint Pwr management: Priority. Lower
number represents "higher" priority, i.e. a gen-set with lower number starts before another one with
higher number. In other words, the setpoint Pwr management: Priority means order in which gen-sets
are started and connected to the bus. An example is shown on the figure below. There are four gen-
sets with following choice of setpoints:
Setpoint
group
Basic
settings
Pwr management
Setpoint
Nomin
power
Pwr
management
#Pwr mgmt
mode
Priority
#PriorityAutoS
wap
#LoadResStr
t X
#LoadResStop
X
Gen-set #1
200 kW
ENABLED
ABS (kW)
4
DISABLED
50 kW
70 kW
Gen-set #2
200 kW
ENABLED
ABS (kW)
3
DISABLED
50 kW
70 kW
Gen-set #3
200 kW
ENABLED
ABS (kW)
2
DISABLED
50 kW
70 kW
Gen-set #4
200 kW
ENABLED
ABS (kW)
1
DISABLED
50 kW
70 kW
Power [% / kW]
Sum of available nominal
power running gen-sets
in PM
Total load of the system
Level to start additional gen-
set Nom Pwr - #LoadResStrt X
Level to stop additional gen-set
Nom Pwr - #LoadResStop X
130
330
150
350
400
Time
Time
Starting
sequence
Gen #4 Priority = 1
Gen #3 Priority = 2
Gen #2 Priority = 3
Starting sequence
Stopping sequence
200
330
350
400
800
Gen #1 Priority = 4
Starting
sequence
Starting
sequence
Stopping
sequence
Stopping
sequence
Stopping
sequence
Figure: Power management example - Priorities

Table of Contents