EasyManua.ls Logo

ComAp InteliMains NT IM-NT-BB - Page 91

ComAp InteliMains NT IM-NT-BB
437 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
91
G1+G2
700
451 .. 650
G3
1000
651 .. 950
G1+G3
1200
951 .. 1150
G2+G3
1500
1151 .. 1450
G1+G2+G3
1700
>1450
Following table describes selected power bands:
Power band
Gen-sets
Nominal power [kW]
Power band range [kW]
#PwrBandContr1
G1
200
0 .. 150
#PwrBandContr2
G2
500
151 .. 450
#PwrBandContr3
G3
1000
451 .. 950
#PwrBandContr4
G2+G3
1500
951 .. 1450
Fixed power band #5
G1+G2+G3
1700
>1450

Table of Contents