InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
94
Following table provide an example of gen-set selection in function of system load evolution. The table
is an example of Efficiency priority optimization function.
System Load
[kW]
Running gen-sets
Description
Total Running
power within PM
[kW]
Relative load of
gen-sets [%]
40

100
40%
60

100
60%
80
[0h]
start
stop
LDS Swap
300
26%
100
[10h]
200
50%
120
[20h]
200
60%
120
[30h] [10h]
Start
stop
RHE Swap
400
30%
120
[20h]
200
60%
140
[30h]
200
70%
180
[40h]
Start
stop
LDS Swap
500
36%
200

300
67%
240

300
80%
280

Start
Gen#5 joins
(LDS)
400
70%
340

400
85%
380
[20h]
start
stop
LDS + RHE
Swap
600
63%
400
500
80%
440
500
88%
480
start
Gen#5 joins
(LDS)
600
80%
540
600
90%
580
[30h]
start
stop
LDS Swap
800
73%
600
700
86%
640
700
91%
680

start
Gen#5 joins
(LDS)
800
85%
740
800
93%
780

[40h]
start
stop
LDS Swap
1000
78%
800
900
89%
840
900
93%
880
start
Gen#5 joins
1000
88%

Table of Contents