InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
97
NOTE:
If more than one binary input for MinRunPower activation is closed MinRunPower setpoint with higher
number is used (i.e. binary inputs with higher number have higher priority). When no binary input is
closed, then minimal running power is 0.
NOTE:
All controllers cooperating together in Power management must have the same Minimal Running
Power set selected.
It is possible to use virtual shared peripheries for distribution of the binary signal activating LBI MinRun
Power 1,2 or 3 among controllers over the CAN bus.
Virtual I/O
BI n
Virtual I/OVirtual I/O
Power
management
Power
management
Power
management
BO n
BI n
#Controller 1 #Controller 2 #Controller 3
Switch for activation
of MiniRun power
set #2
BI n
CAN 2
LBI: MiniRun Power 2
LBI: MiniRun Power 2 LBI: MiniRun Power 2
Figure: Example of using virtual shared peripheries for signal distribution