30 Operating the control software
– Ground FI: with this setting you determine whether the main contactor will
be disengaged whenever the drain pump is activated to prevent current
leakage to the drain, which could trip sensitive GFI circuitry in the building
("On") or not ("Off").
Factory setting: ON
Options: On (main contactor off during draining)
Off (main contactor remains on during draining if
humidifying is in progress)
– Fill Stop: with this setting you determine whether the inlet valve will be
turned off when the heating current equals 95 % of the demand ("On")
during lling to prevent overshooting the demand or not ("Off").
Note: set this setting to "On" if the supply water is of elevated conductivity.
Factory setting: On
Options: On (inlet valve will be turned off when the heating
current equals 95 % of the demand)
Off (Inlet valve remains open until 100 % of the
demand is reached)
– Overcurrent: Caution! Adjust only if instructed by Condair representa-
tive.
Factory setting: 1.5
Setting range: 0.0 ... 2.0
– Low Conductivity: this function allows you to adjusts the end-of-cylinder-life
detection to prevent false end-of-cylinder-life detection when conductivity
of the supply water is less than 250 μS/cm.
Factory setting: Off
Options: On (use when conductivity of the supply water is
less than 250 μS/cm)
Off (use when conductivity of the supply water is
greater than 250 μS/cm)
– Short Cycle: this function allows you to enable ("On") or disable ("Off")
the function that enforces a time delay between the humidier stopping
and restarting steam production (to reduce mechanical wear on contactors
and other peripheral devices).
Note: This function is typically activated with On/Off controllers. It can
also be activated if a high limit humidistat is cycling the humidier on/off
too frequently.
Factory setting: Off
Options: On (the humidier runs in short cycle mode)
Off (the humidier cycles normally)
– Cyl. Type: with this setting you determine whether the Condair EL is
equipped with a replaceable steam cylinder ("Disp.") or a cleanable steam
cylinder ("Clean") .
Factory setting: Disp.
Options: Disp. (replaceable steam cylinder)
Clean (cleanable steam cylinder)