38 Operating the control software
Sequence Interval: with this setting you determine the interval time the
control system compares the operating hours of the cylinders in order to
change the starting order if sequential cylinder rotation activated.
Note: this setting appears only, if the "Sequence Rotation" function is
activated ("On").
Factory setting: 24 hours
Setting range: 24 ... 1000 hours
Linkup Timeout: with this setting you determine, how long the units of a
linkup systems can operate without connection among each other, before
an error message is triggered.
Note: this setting appears only on the "Main" unit of a linkup system.
Factory setting: 60 seconds
Setting range: 60 ... 120 seconds
Zero Out A: this parameter indicates at which percentage of the demand
signal cylinder A is switched on (calculated value).
Full Out A: this parameter indicates at which percentage of the demand
signal cylinder A achieves 100% demand (calculated value).
Zero Out B: this parameter indicates at which percentage of the demand
signal cylinder B is switched on (calculated value).
Full Out B: this parameter indicates at which percentage of the demand
signal cylinder B achieves 100% demand (calculated value).