41Operating the control software
– Primary DNS: with this setting you determine the IP Address of the Primary
Domain Name Server (DNS).
Note: This IP Address for the Primary Domain Name Server is used if "IP
Type" is set (or reverts) to "Fixed".
– Secondary DNS: with this setting you determine the IP Address of the
Secondary Domain Name Server (DNS).
Note: This IP Address for the Secondary Domain Name Server is used if
"IP Type" is set (or reverts) to "Fixed".
– MAC Address: with this setting you determine the MAC Address (Media
Access Control Address) of the Cond air EL.
– Host Name: with this setting you determine the Host Name of the Cond-
air EL.
BMS Timeout
– BMS Timeout: with this setting you determine the maximum time the
humidier will wait with no communication from the BMS network before
a BMS timeout warning is generated. Exceeding the timeout also stops
humidier operation if the signal source of the humidier is set to a BMS
input.
Factory setting: 300 s
Setting range: 1 ... 300 s
Modbus Parameters Tab
– Modbus: with this setting you can activate ("On") or deactivate ("Off")
communication via a Modbus network.
Note: in order to activate the setting of this parameter the Condair EL must
be switched off and on again.
Factory setting: Off
Options: Off or On
The following parameters appear only if the Modbus function is activated.
– Modbus Address: with this setting you determine the Modbus address
for the Condair EL for the communication via a Modbus network.
Factory setting: 10
Setting range: 1 ... 247
– Parity: with this setting you set the parity bit for the data transfer.
Factory setting: Even
Options: None, Even or Odd
– Baudrate: with this setting you set the Baudrate for the data transfer.
Factory setting: 9600
Options: 110, 300, 600, 1200, 2400, 4800, 9600, 19200,
38400, 57600, 76800 or 115200