44
……..connued
MESSAGE DESCRIPTION & SOLUTION
LOW BATTERY
The baery voltage dropped below the trip point (10V). The baery voltage will need to rise
above the recovery voltage before the motor will run again.
Check that the main supply is not switched o or possibly has been le o for an extended
period of me. It can take a at baery up to 7 hours to recover.
Ensure the gate moves easily along it’s enre path. A worn gate, incorrect installaon, worn
wheels etc will put a strain on the baery and can cause a low baery.
If this fault occurs connuously and the baery is older than 1 year it may be a faulty
baery. Go to the ‘Info’ screen, if the charge current (CHARGE I) is low and the baery
voltage (BATT V) is high but drops when the operator is triggered the baery might be
faulty.
Check for loose or corroded baery terminals .
OBSTRUCTION
The controller has detected that the gate has exceeded its running parameters or the gate has
encountered an obstrucon.
Look for an obstrucon and remove.
Run the gate in manual override to ensure the gate is moving easily and freely.
Make sure the maximum pull force is not exceeded.
Make sure the gate wheels move freely.
Check the gate rail for stones or scks.
Make sure the gate enters and leaves the catch bracket easily.
Check that the baery is fully charged.
If everything appears in order it may be necessary to adjust the gate force sengs. Go to Safety
Sengs found under Gate Setup on the LCD screen and adjust the opening and/or closing
forces.
WARNING MESSAGES
MESSAGE DESCRIPTION
TRIGGER The operator received a trigger signal.
PEDESTRIAN The operator received a pedestrian trigger.
LOOP The operator received a loop trigger.
ACTIVATION IS NOT
POSSIBLE WHEN THERE IS
A BATTERY FAULT
CONDITION
If the baery voltage is too low, the controller will not acvate the gate.
ACTIVATION IS NOT
POSSIBLE WHEN THE
SYSTEM IS IN LOCK OUT
The system is currently in Holiday Lockout. Either the Lockout input, Time Manager
or a remote placed the system in Lockout mode. To operate the controller make
sure it is not being held in lockout by any of these.
ENABLE AUTOCLOSE FIRST Condo/Mul User mode cannot be acvated if either Auto Close or Beams Auto
Close is not acve.
DISABLE MULTI USER/
CONDO MODE FIRST
Auto Close cannot be deacvated while Condo/Mul User is acve.
PLEASE RUN SETUP
WIZARD AGAIN
An acon was performed that requires the setup wizard to be run again.
ACTIVATION IS NOT
POSSIBLE WHEN THE LOOP
INPUT IS ACTIVE
While the loop input is held low (either by a loop detector or Time Manager) other
trigger inputs will not close the gate
ACTIVATION IS NOT
POSSIBLE WHEN MULTI
USER MODE IS ACTIVE
While Condo/Mul User mode is acve, other trigger inputs will not close the gate.
The gate will only close with the Auto Close seng.
AUTO LEARN ACTIVE The Auto Learn funcon is currently acve allowing the operator to learn new re-
motes. To cancel Auto Learn simply press the joysck on the Auto Learn icon in the
Remotes menu.
AUTO CLOSE ACTIVE
Auto Close is currently acve.
Connues……...