Group 98: Options
This group congures for options, in particular, enabling serial communication with the drive.
Table 48: Group 98: Options
Code Description Range Resolution Default S
9802 COMM PROT SEL 0…5 1 0
Selects the communication protocol.
0 = NOT SEL – No communication protocol selected.
1 = STD MODBUS – The drive communicates with Modbus via the RS485 channel (X1- communications, terminal).
• See also parameter Group 53 EFB PROTOCOL, page 67.
2 = N2 – Enables eldbus communication with the drive using Metasys N2 protocol via the RS485 serial link (X1-communications terminal).
3 = FLN – Enables eldbus communication with the drive using FLN protocol via the RS485 serial link (X1-communications terminal).
5 = BACNET – Enables eldbus communication with the drive using BACnet protocol via the RS485 serial link (X1-communications terminal).
Daikin uses the "STD Modbus" selection on all VFDs applied
with MicroTech III controls except for RPE and RDE condenser
fans.
aCTual sIgnals and parameTers
www.DaikinApplied.com 69 OM 1190-1 • MD4 VFD