EasyManua.ls Logo

Daikin ACS320 - Analog Output Control; PID Control Setpoint Source; Communication Fault

Daikin ACS320
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Output Control
Using the eldbus for analog output control requires:
Drive parameter values set as dened below.
Fieldbus controller supplied reference word(s) in the
appropriate location. (The location is dened by the
Protocol Reference, which is protocol dependent.)
Table 55: Analog Output Control Protocol Reference
Drive Parameter Value Setting
Protocol Reference
Modbus
N2 FLN BACnet
abb drv dcu prole
1501 AO1 CONTENT SEL
135
(COMM VALUE 1)
Analog Output 1 controlled by
writing to parameter 0135.
0135 COMM VALUE 1 40135 AO14 46 AO0
PID Control Setpoint Source
Use the following settings to select the eldbus as the setpoint source for PID loops:
Table 56: PID Control Setpoint Source Protocol Reference
Drive Parameter Value Setting
Protocol Reference
Modbus
N2 FLN BACnet
abb drv dcu prole
4010
SET POINT SEL
(Set 1)
8 (COMM VALUE 1)
9 (COMM + AI1)
10 (COMM*AI1)
Setpoint is either: Input Reference
2 (+/-/* AI1). Control requires
parameter 1106 value = comm.
Process PID setpoint. Control
requires parameter 1106 value =
pid1 out and parameter 4010 value
= comm.
40003 AO2 61 AV17
4110
SET POINT SEL
(Set 2)
4210
SET POINT SEL (Ext/
Trim)
Communication Fault
When using eldbus control, specify the drive’s action if serial communication is lost.
Table 57: Communication Fault Reference
Drive Parameter Value Description
3018 COMM FAULT FUNC
0 (NOT SEL)
1 (FAULT)
2 (CONST SP7)
3 (LAST SPEED)
Set for appropriate drive response.
3019 COMM FAULT TIME Set time delay before acting on a communication loss.
OM 1190-1 • MD4 VFD 78 www.DaikinApplied.com
fIeldbus ConTrols

Table of Contents

Related product manuals