program feaTures
This section describes program features. For each feature, there is a list of related user settings, actual signals, and
fault and alarm messages.
Programmable Analog Inputs
The drive has two programmable analog voltage/current
inputs. The inputs can be inverted, ltered and the maximum
and minimum values can be adjusted. The update cycle for
the analog input is 8 ms (12 ms cycle once per second). The
cycle time is shorter when information is transferred to the
application program (8 ms -> 2 ms).
Table 2: Programmable Analog Input Settings
Table 3: Programmable Analog Input Diagnostics
Programmable Analog Output
One programmable current output (0…20 mA) is available.
Analog output signal can be inverted, ltered and the maximum
and minimum values can be adjusted. The analog output
signals can be proportional to motor speed, output frequency,
output current, motor torque, motor power, etc. The update
cycle for the analog output is 2 ms.
It is also possible to write a value to an analog output through a
serial communication link.
Table 4: Programmable Analog Output Settings
Table 5: Programmable Analog Output Diagnostics
Parameter Additional Information
Group 11:Reference Select AI as reference source
Group 13: Analog Inputs Analog input processing
3001, 3021, 3022, 3107 AI loss supervision
Group 35: Motor Temp Meas AI in motor temperature measurement
Group 40: Process PID Set 1 …
Group 42: External PID
AI as PID process control reference
or actual value source
Group 44: Pump Protection
AI as pump protection measurement
source
Actual Signal Additional Information
0120, 0121 Analog input values
1401 AI1/A2 signal loss
Alarm
AI1 LOSS / AI2 LOSS
AI1/AI2 signal below AI1/AI2 FAULT
LIMIT (3021/3022)
Fault
AI1 LOSS / AI2 LOSS
AI1/AI2 signal below limit AI1/AI2
FAULT LIMIT (3021/3022)
PAR AI SCALE
Incorrect AI signal scaling (1302 <
1301 or 1305 < 1304)
Parameter Additional Information
Group 15: Analog Outputs AO value selection and processing
Group 35: Motor Temp Meas
AO in motor temperature
measurement
Actual Signal Additional Information
0124 AO value
Fault
PAR AO SCALE
Incorrect AO signal scaling (1503 <
1502)