Analog Input Object Instance Summary
The following table summarizes the Analog Input Objects supported:
Table 64: Analog Input Object Instance Summary
Instance ID Object Name Description Units
Present Value
Access Type
AI0
ANALOG
INPUT 1
This object indicates the value of Analog Input 1. The corresponding drive parameter is 0120. Percent R
AI1
ANALOG
INPUT 2
This object indicates the value of Analog Input 2. The corresponding drive parameter is 0121. Percent R
AO0
AO 1
COMMAND
This object controls Analog Output 1. The corresponding drive parameter is 0135, COMM
VALUE 1. Control requires parameter 1501 value = 135.
Percent C
NOTE: For Present Value Access Types, R = Read-only,W = Writeable, C = Commandable.
Commandable values support priority arrays & relinquish defaults.
fIeldbus ConTrols
www.DaikinApplied.com 85 OM 1190-1 • MD4 VFD