EasyManua.ls Logo

Danfoss AK2-SC 255 - Maintenance Hours

Danfoss AK2-SC 255
206 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RS.8D.M1.22 AK2-SC 255 Reference Manual 167
sensor to a fixed value if for instance, a sensor has
failed and you are awaiting a service replacement.
To set a manual value, select the M from the list box,
then enter the desired value in the Current field,
which becomes a label field as soon as the M is
entered. At the same time, when the M is entered,
the Offset and Input fields no longer appear.
Offset (Label field) A field where you can enter an offset to
adjust the sensors reading when calibrating with
actual temperature as read from a refrigeration
thermometer.
If you change an offset from a negative to a positive
value, the sign will not change until you enter the first
numeral from the keypad.
You can only offset a real sensor; you cannot enter
an offset for a reading being received from another
controller. And you cannot use a large offset to
“fake” a missing sensor.
Input The sensors current electrical value in volts or
ohms, for comparison with a table of standard
values.
Maintenance Hours The Maintenance hours service screen maintains Total Run Hours for each device
or lighting zone (since its first start after configuration), and Maintenance Hours, a
counter that you can reset to zero using the <Clear> button at the bottom of the
screen. The date of last clearing is also displayed.
Bd/Pt Locations This screen is identical in function to the Board & Points screens described in Part I,
Section 1.2, “Configuring Board & Points.”

Table of Contents

Other manuals for Danfoss AK2-SC 255

Related product manuals