RS.8D.M1.22 AK2-SC 255 Reference Manual 47
earlier section on evaporator (defrost) configuration. The screen is not shown here.
Receiver
configuration To configure the receiver, return to the Configure Rack menu, put the cursor on
Receiver, and press ENTER. The screen is as shown below.
Surge control (List box: Yes, No) Whether or not surge control will
be implemented.
Cutin (0.0 to 100.0) The temperature at which the surge
valve opens.
Cutout (0.00 to 100.0) The temperature at which the surge
valve closes.
Liquid level sensor type (List box:)
Sensor input: An analog sensor is used for liquid
level.
On/Off input: A digital sensor is used for liquid level.
None: There is no liquid level sensor monitored.
Heat reclaim
configuration To configure heat reclaim, return to the Configure Rack menu, put the cursor on Heat
Reclaim, and press ENTER. The screen is as shown below.