The fields are as follows:
[Informed adjustment of these settings is best done by
Danfoss-trained technicians.]
Normal Reaction Zone (0.1 to 60.0) The range of pressure on either side of
the target in which the condenser control algorithm
reacts with normal sensitivity.
Plus Zone (10 to 900) The PI algorithm sensitivity when current
control sensor value is above the normal reaction zone.
Minus Zone (10 to 900) (10 to 900) The PI algorithm sensitivity
when current control sensor value is above the normal
reaction zone.
Enviroguard systems The next page is for setpoints that will be used with a Tyler Enviroguard
®
system:
The fields and contents are as follows: