86 AK2-SC 255 Reference Manual RS.8D.M1.22
when the store is closed according to a schedule or
schedules configured in the Store Info screens.
Night setback offset (-50.0 to 50.0) The amount by which the heating
setpoint (set on previous page) is to be lowered during
non-scheduled hours (as set in the Store Info screens).
Minimum ON time (0 to 60) The minimum number of minutes heating
must run after being turned on before being turned off.
Minimum OFF time (0 to 60) The minimum number of minutes heating
must remain off after being turned off before being
turned on.control actions. See preceding two settings.
RTC dehumidification
configuration There are two pages of dehumidification configuration settings:
Dehumidification type (List box: None, Cooling) The type of dehumidification
used.
Aux heat during dehumid (List box: Yes, No) Whether or not auxiliary heat is
allowed during dehumidification.
Control dehumid. on (List box:)
Humidity: Dehumidification will be controlled based
on a specified humidity target. A humidity sensor is
required.
Calc Dewpt: Dehumidification will be controlled
based on a specified dewpoint target, which will be
compared with a dewpoint calculated from zone
temperatuare and humidity. Both zone temperature
and humidity sensors must be installed.
Control dehumid. using (List box, if controlled by dewpoint or humidity only,
and if there are multiple sensors:)
Average: Control will be based on the average of a
group of sensors.
High: The high value of a group of sensors will be
used.