92 AK2-SC 255 Reference Manual RS.8D.M1.22
changed.
No: The input is not configured. Its state can not be
used by the controller.
Rec: The input value is to be received from another
node (other than this RTC board) on the I/O network.
The board and point that is broadcasting the state of
the input must be given in the next column.
AK2-SC 2 55 Bd-Pt (Address field) If the input state is received from
another node on the I/O network, enter here the
address of the point that is to be received.
In the lower half of the screen, the SC 255 Inputs:
Name (Label field, not changeable) The name of the point.
The RTC board’s software can only use the listed
inputs from the I/O network. The names always
appear as in the illustration above, whether the input is
used or not.
Bcast (List field, one for each point:)
No: The input is not configured or its state is not to be
used by the controller.
Rec: The input value is to be received from another
node (other than this RTC board) on the I/O network.
The board and point that is broadcasting the state of
the input must be given in the next column.
On (List field:)
Voltage: The input state will read ON when the point
senses voltage.
No Voltage: The input state will read ON when the
point senses no voltage.
Bd-Pt (Address field) If the input state is received from
another node on the I/O network, enter here the
address of the point that is to be received.
Configuring RTC I/O
variable outputs Here is the screen for variable (analog) outputs, reached with the fourth icon from
left. The names appear if the points are configured.