RS.8D.M1.22 AK2-SC 255 Reference Manual 95
alarm.
SC4 cooling
configuration
No of zone sensors (0 to 5) The number of zone temperature sensors.
Controlling sensor (List box:)
Min Temp: Control will be based on the lowest value
of all of the zone temperature sensors.
Max Temp: Control will be based on the highest
value of all of the zone temperature sensors.
Average: Control will be based on the average of all
the zone temperature sensors.
Zone Temp 4-1 (etc.): (each zone temperature
sensor will be available as a choice in the list) Control
will be based on the single selected sensor.
Num of cooling stages (List box: None, Four) Of the four cooling stages in
the unit, the number to be controlled by the AKC 55.
Either all units are controlled or none are controlled.
Setpoint (0.0 to 100.0) The desired temperature at the control-
ling sensor.
Range +/- (-9.9 to 9.9) The range selected creates a dead band.
For example, if the target is 72 and the range is 2, the
stage will come on at 74, and will not be turned off