Selection table, 380–415 V, 50 Hz
Frequency converter
values
Filter values
Power
rating
Input
current
Current
rating
Ordering numbers Power loss
Acoustic
noise
Enclosure sizes, enclosure protection rating, and fan
concept
T4/T5 380–440 V AHF 005 AHF 010 AHF 005 AHF 010 AHF 005 AHF 010
[kW]
1)
[A] [A] IP00 IP20 IP00 IP20 [W] [W] [dB(A)] IP00 IP20 IP00 IP20
315 590 608 2 x 130B1448 2 x 130B1259 2 x 130B1370 2 x 130B1216 2576 1810 <80
See individual lters
355 647 650 2 x 130B3153 2 x 130B3152 2 x 130B3151 2 x 130B3136 2812 1904 <80
400 684 685
130B1448
+
130B1449
130B1259
+
130B1260
130B1370
+
130B1389
130B1216
+
130B1217
2798 2080 <80
450 779 762 2 x 130B1449 2 x 130B1260 2 x 130B1389 2 x 130B1217 3020 2350 <80
500 857 861
130B1449
+
130B1469
130B1260
+
130B1261
130B1389
+
130B1391
130B1217
+
130B1228
3362 2717 <80
560 964 960 2 x 130B1469 2 x 130B1261 2 x 130B1391 2 x 130B1228 3704 3084 <80
630 1090 1140 3 x 130B1449 3 x 130B1260 3 x 130B1389 3 x 130B1217 4530 3525 <80
710 1227 1240
2 x 130B1449
+
130B1469
2 x 130B1260
+
130B1261
2 x 130B1389
+
130B1391
2 x 130B1217
+
130B1228
4872 3892 <80
800 1422 1440 3 x 130B1469 3 x 130B1261 3 x 130B1391 3 x 130B1228 5556 4626 <80
1000 1675 1720
2 x 130B1449
+
2 x 130B1469
2 x 130B1260
+
2 x 130B1261
2 x 130B1389
+
2 x 130B1391
2 x 130B1217
+
2 x 130B1228
6724 5434 <80
1) kW power ratings in selection table are the actual operating power and not necessarily the type code power rating. Changing operating conditions between HO and NO changes the actual operating
conditions and the lter selection must reect actual operating conditions.
2) Filters are used as paralleling for 355 kW frequency converters.
Table 5.3 380–415 V, 50 Hz
Selection of Advanced Harmo... Design Guide
MG80C502 Danfoss A/S © 10/2016 All rights reserved. 33
5 5