VLT
®
AQUA Drive FC 202
N132 N160
High/normal load HO NO HO NO
(High overload=150% current during 60 s, normal overload=110%
current during 60 s)
Typical shaft output at 525 V [kW] 90 110 110 132
Typical shaft output at 575 V [hp] 125 150 150 200
Typical shaft output at 690 V [kW] 110 132 132 160
Enclosure size D1h/D3h/D5h/D6h
Output current (3-phase)
Continuous (at 525 V) [A] 137 162 162 201
Intermittent (60 s overload) (at 525 V) [A] 206 178 243 221
Continuous (at 575/690 V) [A] 131 155 155 192
Intermittent (60 s overload)(at 575/690 V) [A] 197 171 233 211
Continuous kVA (at 525 V) [kVA] 125 147 147 183
Continuous kVA (at 575 V) [kVA] 131 154 154 191
Continuous kVA (at 690 V) [kVA] 157 185 185 230
Maximum input current
Continuous (at 525 V) [A] 132 156 156 193
Continuous (at 575/690 V) 126 149 149 185
Maximum number and size of cables per phase
- Mains, motor, brake, and load share [mm
2
(AWG)]
2x95 (2x3/0) 2x95 (2x3/0)
Maximum external mains fuses [A]
1)
160 315
Estimated power loss at 575 V [W]
2), 3)
1742 2101 2080 2649
Estimated power loss at 690 V [W]
2), 3)
1800 2167 2159 2740
Eciency
3)
0.98 0.98
Output frequency [Hz] 0–590 0–590
Heat sink overtemperature trip [°C (°F)]
110 (230) 110 (230)
Control card overtemperature trip [°C (°F)]
75 (167) 75 (167)
Table 7.6 Electrical Data for Enclosures D1h/D3h/D5h/D6h, Mains Supply 3x525–690 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor eciency (IE/IE3 border line). Lower eciency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
eciency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Eciency measured at nominal current. For energy
eciency class, see chapter 7.5 Ambient Conditions. For part load losses, see drives.danfoss.com/knowledge-center/energy-eciency-directive/#/.
Specications
VLT
®
AQUA Drive FC 202