EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 301

Danfoss VLT AutomationDrive FC 301 Design Guide

Danfoss VLT AutomationDrive FC 301
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
NOTICE
Protection mode and trip delay features (14-25 Trip Delay
at Torque Limit and 14-26 Trip Delay at Inverter Fault)
may delay the activation of the mechanical brake in an
alarm condition. These features must be disabled in
hoisting applications.
Start
term.18
1=on
0=o
Shaft speed
Start delay time
on
o
Brake delay time
Time
Output current
Relay 01
Pre-magnetizing
current or
DC hold current
Reaction time EMK brake
Par 2-20
Release brake current
Par 1-76 Start current/
Par 2-00 DC hold current
Par 1-74
Start speed
Par 2-21
Activate brake
speed
Mechanical brake
locked
Mechanical brake
free
Par 1-71
Par 2-23
130BA074.12
Illustration 4.2 Mechanical Brake
4.2.13
Closed Loop Mechancial Brake
Control/Hoist Mechanical Brake
The hoist mechanical break control supports the following
functions:
2 channels for mechanical brake feedback to offer
further protection against unintended behaviour
resulting from broken cable.
Monitoring of mechanical brake feedback
throughout the complete cycle. This helps protect
the mechanical brake - especially if more
frequency converters are connected to the same
shaft.
No ramp up until feedback confirms mechanical
brake is open.
Improved load control at stop. If 2-23 Activate
Brake Delay is set too short, W22 is activated and
the torque is not allowed to ramp down.
The transition when motor takes over the load
from the brake can be configured. 2-28 Gain
Boost Factor can be increased to minimise the
movement. For very smooth transition change
the setting from the speed control to the position
control during the change-over.
Set 2-28 Gain Boost Factor to 0 to enable
Position Control during 2-25 Brake
Release Time. This enables parameters
2-30 Position P Start Proportional Gain to
2-33 Speed PID Start Lowpass Filter Time
which are PID parameters for the
Position Control.
Product Features
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
MG33BF02 - Rev. 2013-12-20 41
4 4

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals