EasyManuals Logo

Danfoss VLT AutomationDrive FC 301 Design Guide

Danfoss VLT AutomationDrive FC 301
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #75 background imageLoading...
Page #75 background image
6.2.6 Derating for Ambient Temperature
6.2.6.1 Derating for Ambient Temperature,
Enclosure Type A
60° AVM - Pulse Width Modulation
2
20%
4 6 8
10
12 14 16
40%
60%
80%
100%
110%
I
out
(%)
f
sw
(kHz)
A1-A3 45°C, A4-A5 40°C
A1-A3 50°C, A4-A5 45°C
A1-A3 55°C, A4-A5 50°C
130BA393.10
0
0
Illustration 6.2 Derating of I
out
for Different T
AMB, MAX
for
Enclosure Type A, using 60° AVM
SFAVM - Stator Frequency Asyncron Vector Modulation
2
20%
4 6 8 10 12 14 16
40%
60%
80%
100%
110%
A1-A3 45°C, A4-A5 40°C
A1-A3 50°C, A4-A5 45°C
A1-A3 55°C, A4-A5 50°C
0
0
130BD639.10
I
out
(%)
f
sw
(kHz)
Illustration 6.3 Derating of I
out
for Different T
AMB, MAX
for
Enclosures Type A, using SFAVM
When using only 10 m motor cable or less in enclosure
type A, less derating is necessary. This is due to the fact
that the length of the motor cable has a relatively high
impact on the recommended derating.
60° AVM
2
20%
4 6 8 10 12 14 16
40%
60%
80%
100%
110%
I
out
(%)
A1-A3 45°C, A4-A5 40°C
A1-A3 50°C, A4-A5 45°C
A1-A3 55°C, A4-A5 50°C
0
0
130BA394.10
f
sw
(kHz)
Illustration 6.4 Derating of I
out
for Different T
AMB, MAX
for
Enclosures Type A, using 60° AVM and maximum 10 m motor
cable
SFAVM
2
20%
4 6 8 10 12 14 16
40%
60%
80%
100%
110%
I
out
(%)
A1-A3 45°C, A4-A5 40°C
A1-A3 50°C, A4-A5 45°C
A1-A3 55°C, A4-A5 50°C
0
0
130BD640.10
f
sw
(kHz)
Illustration 6.5 Derating of I
out
for Different T
AMB, MAX
for
Enclosures Type A, using SFAVM and maximum 10 m motor
cable
6.2.6.2
Derating for Ambient Temperature,
Enclosure Types B
Enclosure B, T2, T4 and T5
For the enclosure types B and C the derating also depends
on the overload mode selected in 1-04 Overload Mode
60° AVM - Pulse Width Modulation
2
20%
4 6 8 10 12 14 16
40%
60%
80%
100%
110%
f
sw
(kHz)
45°C
50°C
55°C
130BA402.10
0
0
I
out
(%)
HO
B1
B2
Illustration 6.6 Derating of I
out
for different T
AMB, MAX
for
Enclosure Types B1 and B2, using 60° AVM in High overload
mode (160% over torque)
2
20%
4 6 8 10 12 14 16
40%
60%
80%
100%
110%
f
sw
(kHz)
0
0
I
out
(%)
NO
45°C
50°C
55°C
130BA401.11
B1
B2
Illustration 6.7 Derating of I
out
for different T
AMB, MAX
for
Enclosure Types B1 and B2, using 60° AVM in Normal
overload mode (110% over torque)
Product Specifications
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
MG33BF02 - Rev. 2013-12-20 73
6 6

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals