6.2.3 Ambient Conditions
Environment
Enclosure IP20/Chassis, IP21/Type 1, IP55/ Type 12, IP66/ Type 4X
Vibration test 1.0 g
Max. THVD 10%
Max. relative humidity 5% - 93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class Kd
Ambient temperature Max. 50 °C (24-hour average maximum 45 °C)
Minimum ambient temperature during full-scale operation 0 °C
Minimum ambient temperature at reduced performance - 10 °C
Temperature during storage/transport -25 to +65/70 °C
Maximum altitude above sea level without derating 1000 m
EMC standards, Emission EN 61800-3, EN 55011
1)
EMC standards, Immunity EN61800-3, EN 61000-6-1/2
1) See chapter 5.2.1 EMC Test Results
6.2.4
Cable Specifications
Cable lengths and cross sections for control cables
1)
Max. motor cable length, screened 150 m
Max. motor cable length, unscreened 300 m
Maximum cross section to control terminals, flexible/rigid wire without cable end sleeves 1.5 mm
2
/16 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves 1 mm
2
/18 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar 0.5 mm
2
/20 AWG
Minimum cross section to control terminals 0.25 mm
2
/24 AWG
1) For power cables, see electrical tables in chapter 6.1 Electrical Data.
6.2.5 Control Input/Output and Control Data
6.2.5.1 Digital Inputs
Digital inputs
Programmable digital inputs FC 301: 4 (5)
1)
/FC 302: 4 (6)
1)
Terminal number 18, 19, 27
1)
, 29
1)
, 32, 33
Logic PNP or NPN
Voltage level 0 - 24 V DC
Voltage level, logic'0' PNP < 5 V DC
Voltage level, logic'1' PNP > 10 V DC
Voltage level, logic '0' NPN
2)
> 19 V DC
Voltage level, logic '1' NPN
2)
< 14 V DC
Maximum voltage on input 28 V DC
Pulse frequency range 0-110 kHz
(Duty cycle) Min. pulse width 4.5 ms
Input resistance, R
i
approx. 4
Product Specifications
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
MG33BF02 - Rev. 2013-12-20 69
6 6

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals