5-55 Term. 33 Low Frequency
Range: Function:
100 Hz* [0 - 110000
Hz]
Enter the low frequency
corresponding to the low motor
shaft speed (that is low reference
value) in parameter 5-57 Term. 33
Low Ref./Feedb. Value.
5-56 Term. 33 High Frequency
Range: Function:
100 Hz* [0 - 110000
Hz]
Enter the high frequency
corresponding to the high motor
shaft speed (that is high reference
value) in parameter 5-58 Term. 33
High Ref./Feedb. Value.
5-57 Term. 33 Low Ref./Feedb. Value
Range: Function:
0 Referen-
ceFeedback
Unit*
[-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the low reference value [RPM]
for the motor shaft speed. This is
also the low feedback value, see
also parameter 5-52 Term. 29 Low
Ref./Feedb. Value.
5-58 Term. 33 High Ref./Feedb. Value
Range: Function:
100
Reference-
FeedbackU
nit*
[-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the high reference value
[RPM] for the motor shaft speed.
See also parameter 5-53 Term. 29
High Ref./Feedb. Value.
5-59 Pulse Filter Time Constant #33
Range: Function:
100 ms* [5 - 1000 ms]
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Enter the pulse lter time constant.
The low-pass lter reduces the
inuence and dampens oscillations
on the feedback signal from the
control.
This is an advantage if there is a lot
of noise in the system.
3.7.13 5-6* Pulse Outputs
Parameters for conguring the scaling and output
functions of pulse outputs. The pulse outputs are
designated to terminals 27 or 29. Select terminal 27 output
in parameter 5-01 Terminal 27 Mode and terminal 29 output
in parameter 5-02 Terminal 29 Mode.
Output value
Output
(Hz)
High output
value
P 5-60(term27)
P 5-63(term29)
High freq.
P 5-62(term27)
P 5-65(term29)
130BA089.11
Illustration 3.29 Pulse Outputs
Options for readout output variables
[0] No operation
[45] Bus ctrl.
[48] Bus ctrl. timeout
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque relative to limit
[105] Torque relative to rated
[106] Power
[107] Speed
[113] Ext. Closed Loop
[114] Ext. Closed Loop
[115] Ext. Closed Loop
5-60 Terminal 27 Pulse Output Variable
Option: Function:
[0] * No operation
[45] Bus ctrl.
[48] Bus ctrl.,
timeout
[51] MCO
controlled
[86] Pressure
Sensor 1
[88] Pressure
Sensor 2
[93] Pressure
Sensor 3
[100] Output freq.
0-100
[101] Reference
Min-Max
Parameter Descriptions
VLT
®
HVAC Drive FC 102
102 Danfoss A/S © 10/2019 All rights reserved. M0010001
33