5-60 Terminal 27 Pulse Output Variable
Option: Function:
[102] Feedback
+-200%
[103] Motor cur. 0-
Imax
[104] Torque 0-Tlim
[105] Torque 0-
Tnom
[106] Power 0-Pnom
[107] Speed 0-
HighLim
[113] Ext. Closed
Loop 1
[114] Ext. Closed
Loop 2
[115] Ext. Closed
Loop 3
[186] Pressure
Sensor 4
5-62 Pulse Output Max Freq #27
Range: Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
5000 Hz* [0 - 32000
Hz]
Set the maximum frequency for
terminal 27 corresponding to the
output variable selected in
parameter 5-60 Terminal 27 Pulse
Output Variable.
5-63 Terminal 29 Pulse Output Variable
Option: Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Select the variable for viewing on
terminal 29. Same options and
functions as parameter group 5-6*
Pulse Output.
[0] * No operation
[45] Bus ctrl.
[48] Bus ctrl.,
timeout
[51] MCO
controlled
[86] Pressure
Sensor 1
5-63 Terminal 29 Pulse Output Variable
Option: Function:
[88] Pressure
Sensor 2
[93] Pressure
Sensor 3
[100] Output freq.
0-100
[101] Reference
Min-Max
[102] Feedback
+-200%
[103] Motor cur. 0-
Imax
[104] Torque 0-Tlim
[105] Torque 0-
Tnom
[106] Power 0-Pnom
[107] Speed 0-
HighLim
[113] Ext. Closed
Loop 1
[114] Ext. Closed
Loop 2
[115] Ext. Closed
Loop 3
[186] Pressure
Sensor 4
5-65 Pulse Output Max Freq #29
Range: Function:
5000 Hz* [0 - 32000
Hz]
Set the maximum frequency for
terminal 29 corresponding to the
output variable set in
parameter 5-63 Terminal 29 Pulse
Output Variable.
5-66 Terminal X30/6 Pulse Output Variable
Select the variable for readout on terminal X30/6.
This parameter is active when VLT
®
General Purpose I/O MCB 101
is installed in the frequency converter.
Same options and functions as parameter group 5-6* Pulse
Outputs.
Option: Function:
[0] * No operation
[45] Bus ctrl.
[48] Bus ctrl.,
timeout
[51] MCO
controlled
[86] Pressure
Sensor 1
[88] Pressure
Sensor 2