23-54 Reset Energy Log
Option: Function:
Select [1] Do reset to reset all values
in the energy log counters shown
in parameter 23-53 Energy Log. After
pressing OK, the setting of the
parameter value automatically
changes to [0] Do not reset.
[0] * Do not reset
[1] Do reset
3.21.4 23-6* Trending
Trending is used to monitor a process variable over time
and record how often the data falls into each of 10 user-
dened data ranges. This is a convenient tool to obtain a
quick overview indicating where to focus on improvement
of operation.
2 sets of data for trending can be created to make it
possible to compare current values for a selected operating
variable with data for a certain reference period, for the
same variable. This reference period can be pre-
programmed (parameter 23-63 Timed Period Start and
parameter 23-64 Timed Period Stop). The 2 sets of data can
be read from parameter 23-61 Continuous Bin Data (current)
and parameter 23-62 Timed Bin Data (reference).
It is possible to create trending for the following operation
variables:
Power.
Current.
Output frequency.
Motor speed.
The trending function includes 10 counters (forming a bin)
for each set of data containing the numbers of
registrations reecting how often the operating variable is
within each of 10 pre-dened intervals. The sorting is
based on a relative value of the variable.
The relative value for the operating variable is determined
as:
Actual/rated x 100% - for power and current.
Actual/max x 100% - for output frequency and
motor speed.
The size of each interval can be adjusted individually, but
is 10% for each as default. Power and current can exceed
rated value, but those registrations are included in 90–
100% (MAX) counter.
Relative value
operating variable
Counter 1: +1
Counter 0: +5
Counter 2: +0
Counter 3: +1
Counter 4: +0
Counter 5: +11
Counter 6: +1
Counter 7: +2
Counter 8: +6
Counter 9: +0
130BA281.10
80
70
50
60
30
40
10
20
%
90
100
Illustration 3.70 Time and Relative Values
Once per second, the value of the operating variable
selected is registered. If a value has been registered to
equal 13%, the counter 10 to <20% is updated with the
value 1. If the value stays at 13% for 10 s, 10 is added to
the counter value.
The contents of counters can be shown as bars on the LCP.
Select Quick MenuLoggings: Trending Continued Bin/
Trending Timed Bin/Trending Comparison.
NOTICE
The counters start counting whenever the frequency
converter is powered up. A power cycle shortly after a
reset resets the counters. EEPROM data is updated once
per hour.
23-60 Trend Variable
Option: Function:
Select the required operating
variable to be monitored for
trending.
[0] Power [kW] Power yielded to the motor.
Reference for the relative value is
the rated motor power
programmed in
parameter 1-20 Motor Power [kW] or
parameter 1-21 Motor Power [HP].
The actual value can be read in
parameter 16-10 Power [kW] or
parameter 16-11 Power [hp].
[1] Current [A] Output current to the motor.
Reference for the relative value is
the rated motor current
programmed in
parameter 1-24 Motor Current. The
actual value can be read in
parameter 16-14 Motor current.
[2] * Frequency
[Hz]
Output frequency to the motor.
Reference for the relative value is
the maximum output frequency
programmed in
Parameter Descriptions
VLT
®
HVAC Drive FC 102
222 Danfoss A/S © 10/2019 All rights reserved. M0010001