23-60 Trend Variable
Option: Function:
parameter 4-14 Motor Speed High
Limit [Hz]. The actual value can be
read in parameter 16-13 Frequency.
[3] Motor Speed
[RPM]
Reference for the relative value is
the maximum motor speed
programmed in
parameter 4-13 Motor Speed High
Limit [RPM].
23-61 Continuous Bin Data
Range: Function:
0* [0 -
4294967295 ]
Array with 10 elements ([0]-[9]
below parameter number in
display). Press [OK] and step
between elements with [
▲
] and [
▼
].
10 counters with the frequency of
occurrence for the operating
variable monitored, sorted
according to the following intervals:
•
Counter [0]: 0–<10%.
•
Counter [1]: 10–<20%.
•
Counter [2]. 20–<30%.
•
Counter [3]: 30–<40%.
•
Counter [4]: 40–<50%.
•
Counter [5]: 50–<60%.
•
Counter [6]. 60–<70%.
•
Counter [7]: 70–<80%.
•
Counter [8]. 80–<90%.
•
Counter [9]: 90–<100% or
maximum.
The above minimum limits for the
intervals are the default limits.
These can be changed in
parameter 23-65 Minimum Bin Value.
Starts to count when the frequency
converter is powered up for the
rst time. All counters can be reset
to 0 in parameter 23-66 Reset
Continuous Bin Data.
23-62 Timed Bin Data
Array [10]
Range: Function:
0* [0 -
4294967295 ]
Array with 10 elements ([0]-[9]
below parameter number in
display). Press [OK] and step
between elements with [
▲
] and [
▼
].
10 counters with the frequency of
occurrence for the operating data
23-62 Timed Bin Data
Array [10]
Range: Function:
monitored sorted according to the
intervals as for
parameter 23-61 Continuous Bin
Data.
Starts to count at the date/time
programmed in
parameter 23-63 Timed Period Start,
and stops at the time/date
programmed in
parameter 23-64 Timed Period Stop.
All counters can be reset to 0 in
parameter 23-67 Reset Timed Bin
Data.
23-63 Timed Period Start
Array [10]
Range: Function:
Size
related*
[ 0 - 0 ]
NOTICE
The frequency converter has
no back-up of the clock
function. The set date/time is
reset to default (2000-01-01
00:00) after a power-down
unless a real-time clock-
module with back-up is
installed. Therefore, the
logging is stopped until date/
time is readjusted in
parameter 0-70 Date and Time.
In parameter 0-79 Clock Fault,
it is possible to program a
warning if the clock has not
been set properly, for example
after a power-down.
NOTICE
When mounting VLT
®
Analog
I/O option MCB 109, a battery
back-up of the date and time
is included.
Set the date and time at which the
trending starts the update of the
timed bin counters.
Date format depends on setting in
parameter 0-71 Date Format, and
time format on setting in
parameter 0-72 Time Format.
Parameter Descriptions Programming Guide