36-11 Terminal X49/1 Low Current
Range: Function:
4 mA* [ 0 - par.
36-13 mA]
Enter the current that corresponds
to the low reference value in
parameter 36-14 Term. X49/1 Low
Ref./Feedb. Value.
36-12 Terminal X49/1 High Voltage
Range: Function:
10 V* [ par. 36-10 -
10 V]
Enter the voltage that corresponds
to the high reference value in
parameter 36-15 Term. X49/1 High
Ref./Feedb. Value.
36-13 Terminal X49/1 High Current
Range: Function:
20 mA* [ par. 36-11 -
20 mA]
Enter the current that corresponds
to the high reference value in
parameter 36-15 Term. X49/1 High
Ref./Feedb. Value.
36-14 Term. X49/1 Low Ref./Feedb. Value
Range: Function:
0* [-999999.999
- 999999.999 ]
Enter the reference or feedback
value that corresponds to the
voltage or current value in
parameter 36-10 Terminal X49/1 Low
Voltage or parameter 36-11 Terminal
X49/1 Low Current.
36-15 Term. X49/1 High Ref./Feedb. Value
Range: Function:
100* [-999999.999
- 999999.999 ]
Enter the reference or feedback
value that corresponds to the
voltage or current value in
parameter 36-12 Terminal X49/1 High
Voltage or parameter 36-13 Terminal
X49/1 High Current.
36-16 Term. X49/1 Filter Time Constant
Range: Function:
0.005 s* [0.005 - 10 s] Enter the lter time constant. This
constant is a rst-order digital low-
pass lter time for suppressing
electrical noise in terminal X49/1. A
high value improves dampening
but also increases the delay
through the lter.
36-17 Term. X49/1 Live Zero
Enable live zero monitoring.
Range: Function:
[0] Disabled
[1] * Enabled
36-20 Terminal X49/3 Low Voltage
Range: Function:
0.07 V* [ 0 - par.
36-22 V]
Enter the voltage that corresponds
to the low reference value in
parameter 36-24 Term. X49/3 Low
Ref./Feedb. Value.
3.29.3 36-2* Analog Input X49/3
36-21 Terminal X49/3 Low Current
Range: Function:
4 mA* [ 0 - par.
36-23 mA]
Enter the current that corresponds
to the low reference value in
parameter 36-24 Term. X49/3 Low
Ref./Feedb. Value.
36-22 Terminal X49/3 High Voltage
Range: Function:
10 V* [ par. 36-20 -
10 V]
Enter the voltage that corresponds
to the high reference value in
parameter 36-25 Term. X49/3 High
Ref./Feedb. Value.
36-23 Terminal X49/3 High Current
Range: Function:
20 mA* [ par. 36-21 -
20 mA]
Enter the current that corresponds
to the high reference value in
parameter 36-25 Term. X49/3 High
Ref./Feedb. Value.
36-24 Term. X49/3 Low Ref./Feedb. Value
Range: Function:
0* [-999999.999
- 999999.999 ]
Enter the reference or feedback
value that corresponds to the
voltage or current value in
parameter 36-20 Terminal X49/3 Low
Voltage or parameter 36-21 Terminal
X49/3 Low Current.
36-25 Term. X49/3 High Ref./Feedb. Value
Range: Function:
100* [-999999.999
- 999999.999 ]
Enter the reference or feedback
value that corresponds to the
voltage or current value in
parameter 36-22 Terminal X49/3 High
Voltage or parameter 36-23 Terminal
X49/3 High Current.
36-26 Term. X49/3 Filter Time Constant
Range: Function:
0.005 s* [0.005 - 10 s] Enter the lter time constant. This
constant is a rst-order digital low-
pass lter time for suppressing
electrical noise in terminal X49/3. A
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 263