0-61 Access to Main Menu w/o Password
Option: Function:
[0] * Full access Disables the password dened in
parameter 0-60 Main Menu
Password. If this option is selected,
parameter 0-60 Main Menu
Password, parameter 0-65 Personal
Menu Password, and
parameter 0-66 Access to Personal
Menu w/o Password are ignored.
[1] LCP: Read only Prevents unauthorized editing of
main menu parameters.
[2] LCP: No access Prevents unauthorized viewing and
editing of main menu parameters.
[3] Bus: Read only Provides read-only access to
parameters via eldbus.
[4] Bus: No access Disables access to parameters via
eldbus.
[5] All: Read only Prevents unauthorized editing of
main menu parameters and
provides read-only access to
parameters via eldbus.
[6] All: No access Prevents unauthorized viewing and
editing of Main Menu parameters
0-61 Access to Main Menu w/o Password
Option: Function:
and disables access to parameters
via eldbus.
0-65 Personal Menu Password
Range: Function:
200* [-9999 -
9999 ]
Dene the password for access to
My Personal Menu via the [Quick
Menu] key. If parameter 0-66 Access
to Personal Menu w/o Password is
set to [0] Full access, this parameter
is ignored.
0-66 Access to Personal Menu w/o Password
If parameter 0-61 Access to Main Menu w/o Password is set to [0]
Full access, this parameter is ignored.
Option: Function:
[0] * Full access Disables the password dened in
parameter 0-65 Personal Menu
Password.
[1] LCP: Read only Prevents unauthorized editing of
my personal menu-parameters.
[3] Bus: Read only
[5] All: Read only
Table 3.3 describes how dierent combinations of parameter 0-61 Access to Main Menu w/o Password and
parameter 0-66 Access to Personal Menu w/o Password work when using the LCP.
Combin
ation
number
Option selected in
parameter 0-66 Access to
Personal Menu w/o Password
Option selected in
parameter 0-61 Access to
Main Menu w/o Password
LCP behavior when pressing [Quick Menu] after power-up.
1 [1] LCP: Read only [1] LCP: Read only Users can see My Personal Menu and all other submenus in Quick
Menus. After entering the password from parameter 0-65 Personal
Menu Password, users can edit both parameters inside My Personal
Menu and parameters in all other submenus in Quick Menus.
2 [1] LCP: Read only [2] LCP: No access Users can read My Personal Menu and parameters inside My
Personal Menu only. After entering the password from
parameter 0-65 Personal Menu Password, users can edit and see
parameters inside My Personal Menu only.
3 [1] LCP: Read only [5] All: Read only Same as combination 1.
4 [1] LCP: Read only [6] All: No access Same as combination 2.
5 [2] LCP: No access [1] LCP: Read only Same as combination 1.
6 [2] LCP: No access [2] LCP: No access Users get the Access denied message and the password dialog
appears. Users must enter the password from
parameter 0-60 Main Menu Password, not the password from
parameter 0-65 Personal Menu Password.
7 [2] LCP: No access [5] All: Read only Same as combination 1.
8 [2] LCP: No access [6] All: No access Same as combination 6.
9 [6] All: No access [1] LCP: Read only Same as combination 1.
10 [6] All: No access [2] LCP: No access Same as combination 2.
11 [6] All: No access [5] All: Read only Same as combination 1.
12 [6] All: No access [6] All: No access Same as combination 10.