0-43 [Reset] Key on LCP
Option: Function:
[0] Disabled Select to disable the key.
[1] * Enabled [Reset] key is enabled.
[2] Password Avoid unauthorized resetting. If
parameter 0-43 [Reset] Key on LCP is
included in parameter 0-25 My
Personal Menu, dene the password
in parameter 0-65 Personal Menu
Password. Otherwise, dene the
password in parameter 0-60 Main
Menu Password.
[3] Enabled
without OFF
[4] Password
without OFF
[5] Enabled with
OFF
Pressing the key resets the
frequency converter, but does not
start it.
[6] Password with
OFF
Prevents unauthorized reset. After
authorized reset, the frequency
converter does not start. See option
[2] Password for information on how
to set the password.
0-44 [O/Reset] Key on LCP
Option: Function:
[0] Disabled
[1] * Enabled
[2] Password
0-45 [Drive Bypass] Key on LCP
Option: Function:
[0] Disabled
[1] * Enabled
[2] Password
3.2.9 0-5* Copy/Save
Copy parameters from and to the LCP. Use these
parameters for saving and copying set-ups from 1
frequency converter to another.
0-50 LCP Copy
Option: Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
[0] * No copy
[1] All to LCP Copies all parameters in all set-ups
from the frequency converter
0-50 LCP Copy
Option: Function:
memory to the LCP memory. For
service purposes, copy all
parameters to the LCP after
commissioning.
[2] All from LCP Copies all parameters in all set-ups
from the LCP memory to the
frequency converter memory.
[3] Size indep.
from LCP
Copies only the parameters that are
independent of the motor size. Use
the latest selection to program
several frequency converters with
the same function without
disturbing motor data which is
already set.
[10] Delete LCP
copy data
0-51 Set-up Copy
Option: Function:
[0] * No copy No function.
[1] Copy to set-up
1
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up)
to set-up 1.
[2] Copy to set-up
2
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up)
to set-up 2.
[3] Copy to set-up
3
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up)
to set-up 3.
[4] Copy to set-up
4
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up)
to set-up 4.
[9] Copy to all Copies the parameters in the
present set-up to each of the set-
ups 1 to 4.
3.2.10 0-6* Password
0-60 Main Menu Password
Range: Function:
100* [-9999 -
9999 ]
Dene the password for access to
the Main Menu via the [Main Menu]
key. If parameter 0-61 Access to Main
Menu w/o Password is set to [0] Full
access, this parameter is ignored.
Parameter Descriptions Programming Guide