1-63 Slip Compensation Time Constant
Range: Function:
Size
related*
[0.05 - 5 s]
NOTICE
Parameter 1-63 Slip Compen-
sation Time Constant has no
eect when
parameter 1-10 Motor
Construction = [1] PM, non-
salient SPM.
Enter the slip compensation
reaction speed. A high value results
in a slow reaction, and a low value
results in a quick reaction. If low-
frequency resonance problems
arise, use a longer time setting.
1-64 Resonance Dampening
Range: Function:
Size
related*
[0 - 500 %]
NOTICE
Parameter 1-64 Resonance
Dampening has no eect when
parameter 1-10 Motor
Construction=[1] PM, non-
salient SPM.
Enter the resonance damping value.
Set parameter 1-64 Resonance
Dampening and
parameter 1-65 Resonance
Dampening Time Constant to help
eliminate high-frequency resonance
problems. To reduce resonance
oscillation, increase the value of
parameter 1-64 Resonance
Dampening.
1-65 Resonance Dampening Time Constant
Range: Function:
5 ms* [5 - 50 ms]
NOTICE
Parameter 1-65 Resonance
Dampening Time Constant has
no eect when
parameter 1-10 Motor
Construction = [1] PM, non-
salient SPM.
Set parameter 1-64 Resonance
Dampening and
parameter 1-65 Resonance
Dampening Time Constant to help
eliminate high-frequency resonance
problems. Enter the time constant
that provides the best dampening.
1-66 Min. Current at Low Speed
Range: Function:
Size
related*
[ 1 - 200 %]
NOTICE
Parameter 1-66 Min. Current at
Low Speed has no eect if
parameter 1-10 Motor
Construction = [0] Asynchron.
Enter the minimum motor current
at low speed.
Increasing this current improves
developed motor torque at low
speed. Low speed is here dened
as speeds below 6% of the nominal
motor speed (parameter 1-25 Motor
Nominal Speed) in VVC
+
PM Control.
3.3.9 1-7* Start Adjustments
1-70 Start Mode
Option: Function:
[0] Rotor
Detection
Suitable for all applications where
the motor is known to be standing
still when starting (for example
conveyors, pumps, and non-wind
milling fans).
[1] * Parking If the motor turns at a low speed
(that is lower than 2–5% of the
nominal speed), for example due to
fans with windmilling, select [1]
Parking and adjust
parameter 2-06 Parking Current and
parameter 2-07 Parking Time
accordingly.
[2] Rotor Det. w/
Parking
1-71 Start Delay
Range: Function:
00 s* [0 - 120 s] Enter the time delay between the
start command and the time when
the frequency converter supplies
the power to the motor.
This parameter is related to the
start function selected in
parameter 1-72 Start Function.
1-72 Start Function
Option: Function:
Select the start function during the
start delay. This parameter is linked
to parameter 1-71 Start Delay.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
62 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals