2-11 Brake Resistor (ohm)
Range: Function:
Size
related*
[ 5.00 -
65535.00
Ohm]
Set the brake resistor value in Ω.
This value is used for monitoring
the power to the brake resistor in
parameter 2-13 Brake Power
Monitoring. This parameter is only
active in frequency converters with
an integral dynamic brake.
Use this parameter for values
without decimals. For a selection
with 2 decimals, use
parameter 30-81 Brake Resistor
(ohm).
2-12 Brake Power Limit (kW)
Range: Function:
Size
related*
[ 0.001 -
2000.000 kW]
Parameter 2-12 Brake Power Limit
(kW) is the expected average power
dissipated in the brake resistor over
a period of 120 s. It is used as the
monitoring limit for
parameter 16-33 Brake Energy
Average and thereby species when
a warning/alarm is to be given.
To calculate parameter 2-12 Brake
Power Limit (kW), the following
formula can be used.
P
br, avg
W =
U
br
2
V × t
br
s
R
br
Ω × T
br
s
P
br,avg
is the average power
dissipated in the brake resistor, R
br
is the resistance of the brake
resistor. t
br
is the active breaking
time within the 120 s period, T
br
.
U
br
is the DC voltage where the
brake resistor is active. This
depends on the unit as follows:
T2 units: 390 V
T4 units: 810 V
T5 units: 810 V
T6 units: 943 V/1099 V for D F
frames
T7 units: 1099 V
NOTICE
If R
br
is not known, or if T
br
is
dierent from 120 s, the
practical approach is to run
the brake application, read
parameter 16-33 Brake Energy
Average and then enter this
+ 20% in parameter 2-12 Brake
Power Limit (kW).
2-13 Brake Power Monitoring
Option: Function:
NOTICE
This parameter is only active
in frequency converters with
an integral dynamic brake.
This parameter enables monitoring
of the power to the brake resistor.
The power is calculated based on
the resistance (parameter 2-11 Brake
Resistor (ohm)), the DC-link voltage,
and the resistor duty time.
[0] * O No brake power monitoring is
required.
If power monitoring is set to [0] O
or [1] Warning, the brake function
remains active even if the
monitoring limit is exceeded. This
may lead to thermal overload of
the resistor. It is also possible to
generate a warning via a relay/
digital output. The measuring
accuracy of the power monitoring
depends on the accuracy of the
resistance of the resistor (better
than ±20%).
[1] Warning 120s Activates a warning when the
power transmitted over 120 s
exceeds 100% of the monitoring
limit (parameter 2-12 Brake Power
Limit (kW)).
The warning disappears when the
transmitted power drops below
80% of the monitoring limit.
[2] Trip 120s Trips the frequency converter and
shows an alarm when the
calculated power exceeds 100% of
the monitoring limit.
[3] Warning & trip
120s
Activates both of the above,
including warning, trip, and alarm.
[4] Warning 30s
[5] Trip 30s
[6] Warning & trip
30s
[7] Warning 60s
[8] Trip 60s
[9] Warning & trip
60s
[10] Warning 300s
[11] Trip 300s
[12] Warning & trip
300s
[13] Warning 600s
Parameter Descriptions
VLT
®
HVAC Drive FC 102
72 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals